On July 4th our AC stopped working. I replaced the filter but the inside unit was working fine. It looked like the outside Condenser Unit was to blame as the fan was not spinning and it would only hum and buzz.
This is the Unit that stopped working. Its a fairly large unit as it services a 3 zone system. |
Close up of the unit |
Turned Outdoor disconnect off. (Inside unit is already off and breakers are off as well but to be sure) |
Here is the Label off the old Capacitor |
Ryan wrote down my wiring notes. |
Its about as big as a soda can. For size perspective. |
They did not have
any 370vac 80uf/7.5uf capacitors in stock.
I could have ordered
from amazon but wanted to fix today. They had a 80/10 which might have worked
or might have killed fan. They also had 7.5uf separate unit. I purchased both.
I jumpered the common off the big boy to the little guy and ran the fan off there.
Nothing is hooked up to the 10uf on the big boy.
This is the 7.5uf label. (The little guy) |
This is the soda can size one. |
All wired up. |
This is the top view showing the FAN on the big boy has nothing hooked up. (It is 10uf) |